SYARIKAT SESCO BERHAD
Electricity Consumption Calculator

*Tariff Type : 

*Units Consumed : 

Kwh     Kvarh

   
Where can I find the Kwh and Kvarh figures on my bill?

Your Bill :

How your bill amount was calculated:

      Consumed Amount:
    

Lagging Power Factor(LPF) is calculated with this formula (truncate result to 2 decimal places):
= Kwh / SQRT(Kwh2 + Kvarh2)
=
=     

LPF charge (LPFC) will be imposed where LPF is below 0.85.
LPF is between 0.85 and 0.75 : 
[(0.85 - LPF) x 1.5 x Consumed Amount(RM)] 

LPF is 0.75 and below : 
[ (0.85 - 0.75) x 1.5 x Consumed Amount(RM)] + [(0.75 - LPF) x 3 x Consumed Amount(RM)]

Your LPFC 
=
=

Your Bill
= Consumed Amount(RM) + LPFC
=

Step by step guide on using the bill calculator:
1. Select your Tariff Type from the combo box.
2. Key in your Kwh consumption. Key in your Kvarh consumption. Generally all high consumption consumers(C1, C2, C3, I1, I2, I3) will have Kvarh readings on their meter. Some Domestic consumers may have Kvarh readings as well.
3. Click on the "Calculate bill" button to calculate the bill. To reset the calculator for another bill calculation, click on on the "Reset calculator" button.

Please note :
- C2-Commercial Demand, C3-Commercial Peak/Off Demand, I2-Industrial Demand, and I3-Industrial Peak/Off Peak Demand tariff type bills cannot be calculated from this calculator.
- This calculated bill amount is not the official bill amount payable as it does not take into account the rebates and late payment charges. This facility allows you to understand more on how your bill is calculated. The bill amount payable is the amount shown on your actual bill.